AirSprayTech Academy Certificate Program
Relative-Humidity Testing of Concrete Slabs
Article 06 of 20
In-situ relative-humidity testing evaluates the moisture condition inside a
concrete slab rather than relying only on its surface appearance. Properly performed
testing gives the project team information needed to decide whether a flooring,
coating, adhesive, or moisture-mitigation system can be installed.
Return to the Course Overview
What In-Situ Relative-Humidity Testing Measures
In-situ relative-humidity testing measures the relative humidity of the air within a
prepared hole in a concrete floor slab. The commonly referenced test method is
ASTM F2170.
The test helps evaluate the slab's internal moisture condition. This is important
because a concrete surface can appear dry while deeper portions of the slab contain
substantial moisture.
When an impermeable or low-permeability flooring or coating system is installed, moisture
can redistribute within the slab. An internal relative-humidity measurement can therefore
provide information that a surface-only observation cannot.
Contractor principle: The instrument produces a number. The current
ASTM procedure, project specification, and product manufacturer determine whether that
number is valid and acceptable.
Relative Humidity Is Not Moisture Content
Relative humidity is the amount of water vapor in air compared with the maximum amount
that air can hold at the same temperature. It is expressed as a percentage.
An 85% relative-humidity reading does not mean that the concrete is 85% water. It means
that the air within the test location has reached 85% of its water-vapor capacity at
the measured temperature.
Temperature matters because warm and cool air have different water-vapor capacities.
For this reason, the relative-humidity value and temperature should be recorded together.
Why Internal Testing Is Valuable
A slab drying primarily from the top develops a moisture gradient. The concrete near
the exposed surface can become considerably drier than the concrete deeper within the
slab.
Surface readings may change rapidly with weather, HVAC operation, sunlight, air
movement, grinding, or recent cleaning. Internal relative-humidity testing is intended
to evaluate conditions within the slab at a specified depth.
In-Situ Testing Can Help Identify
- Whether internal slab humidity exceeds the specified system limit
- Differences in moisture conditions across a large floor
- Areas requiring additional investigation
- Whether drying is progressing between separate testing periods
- Whether a moisture-mitigation system may need to be considered
- Conditions that should be documented before installation proceeds
Test Depth Matters
The probe hole must be prepared to the depth required by the current ASTM F2170
procedure. The required depth depends on whether the slab dries from one side or from
two sides.
| Slab Drying Condition |
Common ASTM F2170 Test Depth |
Typical Example |
| Drying from one side |
40% of the slab thickness |
A slab-on-ground drying through its upper surface |
| Drying from two sides |
20% of the slab thickness |
An elevated slab capable of drying from its top and underside |
These percentages are measured from the surface through which the concrete is drying.
The technician must determine the actual slab thickness and drying configuration before
calculating the test depth.
Verify the current standard: Test procedures can be revised. Use the
edition required by the project documents and follow the current written instructions
for test depth, quantity, conditioning, equilibration, calibration, and reporting.
How Many Tests Are Required?
Testing one convenient spot is not enough to characterize a large slab. Moisture
conditions can vary because of slab thickness, placement sequence, exposure, previous
flooring, exterior walls, sunlight, drainage, and building operation.
ASTM F2170 establishes a minimum number of test locations based on floor area. The
commonly used minimum is three test locations for the first 1,000 square feet and at
least one additional location for each additional 1,000 square feet.
Project specifications, manufacturers, owners, or observed site conditions may require
more tests. Additional locations should be considered near exterior walls, wet areas,
cracks, drains, plumbing, previous failures, and areas with different construction or
exposure histories.
Building Service Conditions
The building environment influences the slab's moisture condition. Testing performed
in an open or unconditioned building may not represent the conditions that will exist
after occupancy.
The space should be maintained at the temperature and relative humidity expected during
normal service for the period required by the test method and project documents.
If normal service conditions cannot be achieved, the specification and current standard
should be consulted before testing proceeds.
Record the Environmental Conditions
- Ambient air temperature
- Ambient relative humidity
- Concrete surface temperature
- Heating, ventilation, and air-conditioning status
- Whether doors and windows are open or closed
- Recent rain, flooding, cleaning, or water exposure
- Dates when normal service conditions were established
Selecting Test Locations
Test locations should represent the floor area—not merely the easiest places to drill.
A written plan helps prevent convenient locations from replacing representative ones.
Avoid hidden electrical conduits, post-tensioning cables, embedded heating systems,
plumbing, reinforcing steel, and other concealed components. Review drawings and use
appropriate scanning or locating procedures before drilling.
Locations That May Require Special Attention
- Areas near exterior walls and loading doors
- Below-grade or perimeter areas
- Locations around drains and plumbing penetrations
- Previously failed flooring or coatings
- Areas exposed to rain or flooding
- Different concrete placements or slab thicknesses
- Sections previously covered by low-permeability materials
- Visible dampness, staining, efflorescence, cracks, or joints
Basic Testing Sequence
-
Review the governing requirements. Identify the required ASTM
edition, product limits, test quantity, environmental conditions, and tester
qualifications.
-
Prepare a test-location plan. Mark each location with a unique
identification number and record it on a floor plan.
-
Determine slab thickness and drying condition. Calculate the
required hole depth using the applicable procedure.
-
Check for embedded hazards. Review drawings and scan or locate
utilities and reinforcing components as required.
-
Drill the hole. Use the specified diameter and depth while
controlling concrete dust.
-
Clean the hole. Remove drilling dust according to the test-device
and ASTM instructions.
-
Install and seal the sleeve. The sleeve must isolate the test depth
from ambient room air.
-
Allow the required equilibration period. Do not record the official
result before the minimum time required by the current standard.
-
Insert or read the sensor. Follow the sensor manufacturer's
instructions without introducing outside air unnecessarily.
-
Record and report the result. Document relative humidity,
temperature, location, time, equipment, calibration, and site conditions.
Equilibration Cannot Be Rushed
Drilling exposes concrete at the selected depth to the surrounding environment. The
sealed test hole must be allowed to equilibrate before the official reading is taken.
ASTM F2170 currently requires a minimum equilibration period before recording test
results. The technician must confirm the exact requirement in the edition governing
the project. A reading taken too soon may not represent the required equilibrium
condition.
Do not shorten the test: A preliminary reading may be useful for
observation, but it must not be reported as an ASTM F2170 result unless every required
procedure and time period has been satisfied.
Probe Calibration and Verification
Sensors must meet the accuracy and calibration requirements of the current test
standard. Calibration documentation should be current, traceable to the probe or sensor,
and retained with the project records.
Record the equipment manufacturer, model, probe identification, calibration or
verification information, and the instrument used to read the sensor. Damaged,
contaminated, expired, or questionable equipment should not be used.
Follow the probe manufacturer's storage, conditioning, reuse, and verification
instructions. Do not assume that every sensor system has the same procedure.
Interpreting the Results
ASTM F2170 explains how to obtain an in-situ relative-humidity measurement. It does not
establish one universal passing value for every coating, flooring material, adhesive,
or membrane.
The measured result must be compared with the most restrictive applicable limit stated
in the project specification and the current technical information for the complete
proposed system.
| Result Situation |
Contractor Response |
| All readings are within the approved system limit |
Confirm that every other substrate and environmental requirement is also
satisfied before proceeding.
|
| One or more readings exceed the limit |
Document the results, notify the responsible party, and obtain written
direction before installation.
|
| Results vary greatly across the floor |
Investigate slab construction, water sources, exposure history, and the
need for additional test locations.
|
| Conditions changed after testing |
Determine whether retesting is required before installation.
|
| No published system limit is available |
Request written guidance from the manufacturer or specification authority.
|
A Passing RH Test Is Not a Complete Clearance
Relative-humidity testing addresses the internal moisture condition of the slab at the
test locations and time. It does not prove that every other installation requirement
has been met.
The contractor may still need to evaluate surface strength, profile, cleanliness,
porosity, pH, soluble salts, oil, curing compounds, sealers, cracks, joints, temperature,
dew point, and active water intrusion.
Important limitation: An acceptable in-situ RH result does not rule out
condensation, plumbing leakage, exterior water intrusion, active hydrostatic pressure,
or future changes in building conditions.
Common Testing Errors
- Testing before the building reaches the required service conditions
- Using too few test locations
- Selecting only convenient or apparently dry areas
- Failing to confirm the slab thickness
- Drilling to the wrong depth
- Leaving drilling dust in the hole
- Failing to seal the sleeve from room air
- Recording readings before the required equilibration period
- Using equipment without current calibration documentation
- Failing to record temperature with relative humidity
- Comparing results with the wrong product limit
- Reporting a screening measurement as an ASTM-compliant test
Reporting Requirements
A useful report should allow another qualified person to understand what was tested,
where it was tested, how it was tested, and what conditions existed.
Include the Following Information
- Project name, address, and test date
- Name and qualifications of the testing technician
- ASTM standard and edition used
- Floor area and required number of tests
- Unique identification for every test location
- Floor plan showing the test locations
- Slab thickness and calculated test depth
- Whether the slab dries from one side or two sides
- Drilling and probe-installation date and time
- Reading date and time
- Relative humidity and temperature at each location
- Ambient temperature and relative humidity
- HVAC and building-service conditions
- Instrument model, sensor identification, and calibration information
- Visible moisture, damage, cracks, joints, or other unusual conditions
- Applicable acceptance criteria and the source of those criteria
Who Should Perform the Testing?
Some project specifications require testing by an independent agency or a qualified
technician. The International Concrete Repair Institute offers a Concrete Slab Moisture
Testing certification program covering ASTM moisture-test procedures.
Independence can be valuable when test results will determine whether a large
installation proceeds or when warranty and liability issues are significant. Regardless
of who performs the work, the required procedure must be followed and documented.
Safety During Probe Installation
Drilling concrete can expose workers to respirable crystalline silica. Follow applicable
OSHA requirements, the project exposure-control plan, and the equipment manufacturer's
instructions. Use appropriate dust collection, HEPA-filtered equipment, work practices,
respiratory protection when required, eye protection, hearing protection, and other
personal protective equipment.
Concrete slabs may contain electrical conduits, post-tensioning cables, radiant-heating
components, plumbing, and reinforcing steel. Striking these components can cause serious
injury and property damage. Review available drawings and use approved locating
procedures before drilling.
Contractor Pre-Test Checklist
- Obtain the current governing ASTM test procedure.
- Confirm whether certified or independent testing is required.
- Verify that the building is at the required service conditions.
- Determine the total floor area and minimum number of tests.
- Identify the acceptance limits for every component in the system.
- Prepare a representative test-location plan.
- Confirm slab thickness and drying configuration.
- Locate embedded utilities and structural components.
- Verify equipment condition and calibration documentation.
- Prepare silica-dust controls and required PPE.
- Schedule the required equilibration period.
- Prepare a complete reporting form before testing begins.
Knowledge Check
1. What does an in-situ RH test measure?
Answer: It measures the relative humidity and temperature within a
prepared and sealed test location inside the concrete slab.
2. Does an 85% RH result mean that concrete is 85% water?
Answer: No. It describes the amount of water vapor in the air at
the test location compared with that air's capacity at the measured temperature.
3. Why must the slab thickness be known?
Answer: The required test-hole depth is calculated as a percentage
of the slab thickness and depends on whether the slab dries from one or two sides.
4. Does ASTM F2170 establish one passing limit for every floor system?
Answer: No. Acceptance limits come from the project specification
and the manufacturers of the complete proposed system.
5. Can a reading taken immediately after drilling be reported as the final ASTM result?
Answer: No. The test location must be prepared, sealed, and allowed
to equilibrate for the period required by the current standard.
6. What major safety hazards are associated with drilling probe holes?
Answer: Respirable crystalline silica and contact with embedded
electrical lines, post-tensioning cables, heating systems, plumbing, or other
concealed components.
Key Takeaway
In-situ relative-humidity testing provides valuable information about moisture
inside a concrete slab, but reliable results require the correct test depth,
representative locations, proper conditioning, sufficient equilibration, calibrated
equipment, and complete documentation. The measured values must then be compared
with the written requirements of the entire proposed coating or flooring system.
Technical References
Use the edition required by the project specification and verify that testing personnel
have access to the complete current procedure.
-
ASTM F2170 - Standard Test Method for Determining Relative Humidity
in Concrete Floor Slabs Using In Situ Probes.
-
ASTM F710 - Standard Practice for Preparing Concrete Floors to
Receive Resilient Flooring.
-
ASTM F1869 - Standard Test Method for Measuring Moisture Vapor
Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride.
-
ASTM F2659 - Standard Guide for Preliminary Evaluation of
Comparative Moisture Condition of Concrete, Gypsum Cement, and Other Floor Slabs
and Screeds Using a Non-Destructive Electronic Moisture Meter.
-
ICRI Concrete Slab Moisture Testing Program - Education and
certification for technicians performing standardized concrete slab moisture tests.
-
OSHA 29 CFR 1926.1153 - Respirable Crystalline Silica standard for
construction.
-
Current technical data sheets and installation instructions issued by the specified
coating, flooring, adhesive, primer, and moisture-mitigation system manufacturers.
These references provide technical guidance but do not replace the project specification,
applicable regulations, manufacturer requirements, or evaluation by a qualified
professional. Final testing, system-selection, and installation decisions must be based
on current documents and actual site conditions.
Coming Next
Article 07 of 20 - Calcium-Chloride Moisture-Vapor-Emission Testing
Copyright © 2026 Azimuth Spray Systems, LLC. All Rights Reserved.
No part of this article may be reproduced, copied, distributed, republished,
stored, transmitted, or used in any form or by any means without prior written
permission from Azimuth Spray Systems, LLC, except for brief quotations used with
proper attribution.
AirSprayTech.com - The Finishing Authority®