Commercial and Industrial Floor Coatings for Professional Contractors
Article 23 of 24
Floor-Coating Inspection, Testing, Defects, and Repairs
Finding Problems Early and Correcting Their Causes
Quality control does not begin after the final coat is installed.
Professional floor-coating inspection starts with the concrete and
continues through preparation, mixing, application, cure, final
testing, repair, and acceptance.
Inspection Is a Process, Not a Final Walkthrough
A final inspection can identify visible defects, but it cannot
reconstruct conditions that were never measured or work that was
covered by later coats. Once a flooring system is complete, the
concrete profile, repair preparation, primer coverage, embedded
aggregate, and individual layer thicknesses may no longer be visible.
Each stage should therefore be inspected and accepted before it is
covered. The contractor should record materials, batch numbers,
mixing times, environmental conditions, application quantities,
coverage, cure intervals, testing, and repairs.
Good documentation protects the owner and the contractor. It shows
what was done, where it was done, which conditions existed, and how
the completed work was evaluated.
Four Stages of Floor-Coating Inspection
1. Pre-Installation
Confirm the concrete condition, moisture results,
contamination, repairs, joints, access, environmental
controls, materials, equipment, and approved system.
2. Surface Preparation
Verify cleanliness, soundness, surface profile, dust removal,
repair acceptance, edge preparation, and detail readiness.
3. Application
Observe mixing, batch control, coverage, film thickness,
aggregate distribution, recoat timing, workmanship, and
environmental conditions.
4. Final Acceptance
Inspect appearance, cure, texture, continuity, adhesion,
thickness, details, repairs, cleanliness, and readiness for
the intended service.
Pre-Installation Inspection
The contractor should inspect the work area before mobilizing
application crews. Existing conditions should be documented with
written notes, marked drawings, test reports, and dated photographs.
- Concrete age, condition, strength, and previous repairs
- Cracks, joints, spalls, delamination, and surface laitance
- Oil, grease, chemicals, curing compounds, sealers, and adhesives
- Moisture test locations, methods, conditions, and results
- Floor flatness, slope, drainage, and standing-water areas
- Drains, penetrations, equipment bases, walls, and transitions
- Ambient and concrete temperature, humidity, and dew point
- Required mockups, test areas, colors, textures, and acceptance criteria
Conditions outside the contract requirements should be reported in
writing before work proceeds. Beginning installation without
documenting an unacceptable substrate may transfer unnecessary risk
to the flooring contractor.
Inspecting Surface Preparation
Prepared concrete should be clean, sound, dry as required, and
uniformly profiled for the selected system. The correct profile
exposes sound concrete without unnecessarily damaging the slab.
Preparation Acceptance Questions
- Has weak laitance and unsound concrete been removed?
- Does the surface match the specified concrete surface profile?
- Have oil, grease, chemicals, adhesives, and other contaminants been removed?
- Are edges, corners, drains, and vertical surfaces properly prepared?
- Has dust been removed using suitable industrial vacuum equipment?
- Are cracks, joints, and repairs ready to receive the flooring system?
- Has the concrete been damaged by overly aggressive preparation?
- Have all required tests and inspections been documented?
Preparation acceptance should occur before primer application.
Photographs and written records should include representative floor
areas as well as cracks, drains, edges, repairs, and transitions.
Application Quality-Control Checks
| Inspection Point |
What to Verify |
Why It Matters |
| Material identity |
Correct product, component, color, batch, and expiration status |
Prevents incompatible or incorrect materials from entering the system |
| Mix ratio |
Complete units or accurately proportioned components |
Incorrect ratios can prevent proper cure and property development |
| Mixing |
Correct equipment, speed, time, sequence, and container scraping |
Reduces unmixed material, air entrainment, and inconsistent cure |
| Environmental conditions |
Air temperature, surface temperature, humidity, and dew point |
Conditions affect condensation, flow, working time, and cure |
| Coverage and thickness |
Area covered, material consumed, wet film, and system build |
Under-application may reduce performance and hide defects poorly |
| Aggregate |
Correct type, cleanliness, broadcast rate, and distribution |
Aggregate affects thickness, texture, wear, and slip resistance |
| Recoat interval |
Minimum and maximum times for each floor section |
Incorrect timing can cause trapped material or poor intercoat adhesion |
| Workmanship |
Uniformity, edges, seams, roller marks, bubbles, debris, and missed areas |
Early correction is easier before the coating cures or is covered |
Common Floor-Coating Defects
A defect is a visible or measurable condition that differs from the
approved requirement. The appearance of a defect may suggest a cause,
but diagnosis should be based on evidence rather than appearance
alone.
Pinholes and Bubbles
Possible causes include concrete outgassing, air introduced
during mixing, porous concrete, incorrect rolling, excessive
film thickness, or unsuitable environmental conditions.
Blisters
Possible causes include moisture vapor, osmotic pressure,
contamination, trapped solvent or water, poor adhesion, and
application over an unacceptable substrate.
Delamination
Possible causes include weak concrete, laitance,
contamination, insufficient profile, condensation, missed
recoat windows, and incompatible materials.
Soft or Uncured Areas
Possible causes include incorrect proportioning, incomplete
mixing, wrong components, low temperature, contamination, or
application beyond usable working time.
Fish Eyes and Craters
Possible causes include silicone, oil, grease, cleaning
residue, airborne contamination, or poor surface wetting.
Uneven Color or Gloss
Possible causes include batch variation, incomplete mixing,
unequal thickness, inconsistent rolling, different cure
conditions, or contamination.
Peeling at Edges
Possible causes include weak terminations, insufficient edge
preparation, impact, water intrusion, feathered coating
edges, or movement at transitions.
Cracking
Possible causes include concrete movement, reflective
cracking, shrinkage, structural movement, thermal stress,
incorrect joint treatment, or an overly rigid repair.
Diagnose the Cause Before Repairing the Symptom
A blister can be cut out and filled, but the repair may fail again if
moisture vapor, contamination, or poor preparation remains beneath
it. A crack can be coated over, but it may reflect through again if
the crack is moving.
Defect investigation should determine:
- Where the defect occurs and whether it follows a pattern
- Which flooring layer failed
- Whether the failure is adhesive, cohesive, or within the concrete
- Whether moisture, contamination, movement, or chemical exposure is present
- Whether mixing, coverage, temperature, or recoat records reveal a connection
- Whether the condition is isolated or representative of a larger problem
The visible edge of a defect may not show its full extent.
Sounding, probing, adhesion testing, moisture evaluation, sample
removal, or other investigation may be needed to establish repair
boundaries.
Useful Inspection and Testing Methods
| Method |
Purpose |
Important Limitation |
| Visual inspection |
Identifies appearance, contamination, missed areas, texture, and visible defects |
Cannot confirm hidden bond strength, moisture, or complete cure |
| Concrete surface-profile comparison |
Compares prepared concrete with recognized profile references |
Requires representative inspection across the complete floor |
| Wet-film measurement |
Checks applied thickness while material is wet |
May be difficult on textured or aggregate-filled systems |
| Material usage calculation |
Compares installed area with the quantity of material consumed |
Does not show local thin or thick areas |
| Pull-off adhesion testing |
Measures tensile adhesion strength and identifies the failure plane |
Is destructive and requires proper test locations and repairs |
| Holiday or continuity testing |
Locates discontinuities in suitable nonconductive lining systems |
Voltage and procedure must match the system thickness and specification |
| Hardness or cure evaluation |
Assesses whether material has developed expected cure properties |
Results must be interpreted using the product and approved procedure |
| Moisture testing |
Evaluates moisture conditions in or at the concrete slab |
Different tests measure different conditions and are not interchangeable |
Testing Floor-Coating Thickness
Measuring thickness on concrete is more difficult than measuring a
coating on smooth metal. Concrete is rough and variable, and many
flooring systems contain aggregate or multiple layers.
Contractors commonly control thickness through a combination of:
- Measured floor area
- Known material volume
- Specified coverage rate
- Wet-film measurements where practical
- Placement gauges or depth checks for thicker systems
- Core or sample measurements when specified
- Recorded aggregate and resin consumption
Material usage alone is not enough. Extra material around drains,
cracks, coves, low areas, and waste can make the average usage appear
correct while portions of the floor remain thin.
Adhesion Testing
Pull-off testing can help evaluate the tensile bond between the
flooring system and concrete. A loading fixture is bonded to the
surface, the coating is cut around the fixture when required, and
tensile force is applied perpendicular to the floor.
The reported strength is important, but the failure location is also
critical. Failure may occur:
- Within the concrete
- At the concrete-to-primer interface
- Within one of the flooring layers
- Between flooring layers
- Within the adhesive used to attach the testing fixture
Test frequency, locations, acceptance values, concrete condition,
equipment, adhesive cure, cutting procedure, and repair method should
be agreed upon before testing begins.
Holiday and Continuity Testing
Holiday testing is used on certain nonconductive coating and lining
systems to locate pinholes, voids, or discontinuities. It is most
commonly associated with systems intended to provide continuous
protection against liquid or chemical exposure.
The test method and voltage must be appropriate for the coating type,
thickness, substrate, and specification. Excessive voltage or an
unsuitable method can damage the system. Testing should be performed
only after the coating has cured sufficiently.
Important: Do not perform holiday testing simply
because a tester is available. Obtain the flooring manufacturer's
written approval and follow the specified test method, voltage,
cure time, and repair procedure.
Developing a Repair Procedure
Repairs should restore the required bond, thickness, continuity,
texture, chemical resistance, appearance, and cleanability. The
written procedure should identify:
- The confirmed or suspected cause of the defect
- The boundaries of unsound or unacceptable material
- The method for removing defective material
- The required edge geometry and surface preparation
- The repair materials and installation sequence
- Environmental and substrate conditions
- Recoat and cure requirements
- Final inspection and testing
Repair edges should not be left as thin, weak feathers unless the
repair system specifically permits that detail. Saw-cut, keyed, or
otherwise defined terminations may be required to provide a durable
transition.
Repair Appearance and Owner Expectations
A structurally sound repair may remain visible. Differences in age,
batch, texture, aggregate distribution, color, gloss, lighting, and
application method can make an isolated repair noticeable.
Before repairing a prominent area, the contractor and owner should
agree whether the objective is:
- Functional restoration only
- A localized color- and texture-matched repair
- Recoating to natural boundaries
- Recoating the entire room or floor area
Expectations should be documented before work begins. Terms such as
invisible repair or perfect match should be avoided unless a
representative mockup proves that result is achievable.
Practical Contractor Checklist
- Establish inspection and acceptance criteria before mobilization.
- Document existing concrete conditions and previous repairs.
- Record moisture testing, environmental conditions, and surface profile.
- Inspect each stage before it is covered by the next layer.
- Track products, batch numbers, mix times, quantities, and coverage.
- Record recoat times for each floor section.
- Correct bubbles, pinholes, debris, and missed areas while access remains practical.
- Identify the failure plane and underlying cause before developing a repair.
- Obtain manufacturer guidance for uncertain defects or major repairs.
- Define repair boundaries, materials, preparation, and acceptance tests.
- Discuss the expected appearance of repaired areas with the owner.
- Complete and document final inspection before releasing the floor.
Safety and Professional Responsibility
Inspection and repair work can involve cutting, grinding, drilling,
solvents, reactive resins, electrical test equipment, and exposure to
operating facilities. Follow current safety data sheets, equipment
instructions, respiratory-protection requirements, dust-control
procedures, lockout/tagout rules, and site-specific safety plans.
Testing should be performed by qualified personnel using suitable,
calibrated, and verified equipment. The contractor should not alter
test locations, acceptance values, or procedures merely to obtain a
passing result.
Key Takeaway
The best inspection program finds problems while they can still be
corrected. Inspect every stage, record the conditions, use
appropriate tests, diagnose causes rather than symptoms, and repair
the floor using a written procedure with defined acceptance
requirements.
Knowledge Check
1. Why is final inspection alone insufficient?
Later layers hide the concrete profile, repairs, primer, embedded
aggregate, and earlier coats. Each stage must be inspected before
it is covered.
2. Why should the failure plane be recorded during adhesion testing?
The failure location helps determine whether the weakness is
within the concrete, at the concrete-to-coating interface,
within a flooring layer, or between layers.
3. Why is material usage not enough to confirm uniform floor thickness?
Waste and extra material used at cracks, drains, coves, and low
areas may make average consumption appear correct while other
portions remain below the required thickness.
4. What should be determined before repairing a blister or delaminated area?
The underlying cause and the complete extent of unsound material
should be determined. Repairing only the visible symptom may
allow the failure to return.
5. Why should repair appearance be discussed with the owner in advance?
A functional repair may remain visible because of differences in
color, gloss, texture, aggregate, application, or material age.
The expected appearance and repair boundaries should be agreed
upon before work begins.
Technical References
-
ASTM D4258, Standard Practice for Surface Cleaning Concrete for
Coating.
-
ASTM D4259, Standard Practice for Abrading Concrete.
-
ASTM D4263, Standard Test Method for Indicating Moisture in
Concrete by the Plastic Sheet Method.
-
ASTM F2170, Standard Test Method for Determining Relative
Humidity in Concrete Floor Slabs Using In Situ Probes.
-
ASTM D4414, Standard Practice for Measurement of Wet Film
Thickness by Notch Gages.
-
ASTM D7234, Standard Test Method for Pull-Off Adhesion Strength
of Coatings on Concrete Using Portable Pull-Off Adhesion Testers.
-
ASTM D4787, Standard Practice for Continuity Verification of
Liquid or Sheet Linings Applied to Concrete Substrates.
-
ICRI Technical Guideline No. 310.2R, Selecting and Specifying
Concrete Surface Preparation for Sealers, Coatings, Polymer
Overlays, and Concrete Repair.
-
ICRI Concrete Surface Profile comparator chips and related
surface-preparation guidance.
-
Current technical data sheets, safety data sheets, application
instructions, repair procedures, and written recommendations
supplied by the flooring-system manufacturer.
Standards and manufacturer documents may be revised. Confirm that the
current edition and the correct project-specified requirements are
being used.
| Related Articles |
> Academy Series | Five Professional Finishing Certificate Programs
> The Language of Finishing: A Paint and Coatings Industry Glossary
> The Language of Finishing: Paint and Coatings Glossary A–B
> The Language of Finishing: Paint and Coatings Glossary C–D
> The Language of Finishing: Paint and Coatings Glossary E–F
> The Language of Finishing: Paint and Coatings Glossary G–H
> The Language of Finishing: Paint and Coatings Glossary I–K
> The Language of Finishing: Paint and Coatings Glossary L–M
> The Language of Finishing: Paint and Coatings Glossary N–O
> The Language of Finishing: Paint and Coatings Glossary P–Q
> The Language of Finishing: Paint and Coatings Glossary R
> The Language of Finishing: Paint and Coatings Glossary S
> The Language of Finishing: Paint and Coatings Glossary T
> The Language of Finishing: Paint and Coatings Glossary U–V
> The Language of Finishing: Paint and Coatings Glossary W–Z
> The Language of Finishing: Coatings Standards and Acronyms
> Airless Spraying - From Pump to Pattern
> Airless Spraying—From Pump to Pattern | Article 01 of 18
How Airless Spray Equipment Works
> Airless Spraying—From Pump to Pattern | Article 02 of 18
How to Read an Airless Spray Tip Number
> Airless Spraying—From Pump to Pattern | Article 03 of 18
How to Choose the Correct Airless Tip Size
> Airless Spraying—From Pump to Pattern | Article 04 of 18
Understanding Airless Fan Width and Orifice Size
> Airless Spraying—From Pump to Pattern | Article 05 of 18
The Right Way to Set Airless Spray Pressure
> Airless Spraying—From Pump to Pattern | Article 06 of 18
The Perfect Airless Spray Pattern
> Airless Spraying—From Pump to Pattern | Article 07 of 18
Why an Airless Spray Pattern Develops Tails
> Airless Spraying—From Pump to Pattern | Article 08 of 18
How Tip Wear Wastes Paint and Changes the Pattern
> Airless Spraying—From Pump to Pattern | Article 09 of 18
Matching the Tip to the Sprayer’s Capacity
> Airless Spraying—From Pump to Pattern | Article 10 of 18
How Airless Hose Size and Length Affect Performance
> Airless Spraying—From Pump to Pattern | Article 11 of 18
How to Prime and Start an Airless Sprayer
> Airless Spraying—From Pump to Pattern | Article 12 of 18
Professional Airless Spray-Gun Technique
> Airless Spraying—From Pump to Pattern | Article 13 of 18
How to Shut Down, Flush, and Store an Airless Sprayer
> Airless Spraying—From Pump to Pattern | Article 14 of 18
Airless Troubleshooting: When the Pump Will Not Prime
> Airless Spraying—From Pump to Pattern | Article 15 of 18
Airless Troubleshooting: Surging, Pulsing, and Pressure Loss
> Airless Spraying—From Pump to Pattern | Article 16 of 18
Electric, Gas, or Pneumatic Airless Equipment
> Airless Spraying—From Pump to Pattern | Article 17 of 18
Choosing the Right Airless Sprayer for the Work
> Airless Spraying—From Pump to Pattern | Article 18 of 18
Airless Safety: Understanding Injection-Injury Hazards
> Airless Spraying-From Pump to Pattern
Certificate of Completion
> Airless Spraying—From Pump to Pattern | Final Assessment
> Powder Coating - From Particle To Performance
> Powder Coating—From Particle to Performance | Article 01 of 32 | The History of Powder Coating
> Powder Coating—From Particle to Performance | Article 02 of 32 | What Powder Coating Is—and What It Is Not
> Powder Coating—From Particle to Performance | Article 03 of 32 | What Is Inside a Powder Coating?
> Powder Coating—From Particle to Performance | Article 04 of 32 | How Powder Coating Is Manufactured
> Powder Coating—From Particle to Performance | Article 05 of 32 | Thermoset Versus Thermoplastic Powder Coatings
> Powder Coating—From Particle to Performance | Article 06 of 32 | Epoxy, Polyester, and Epoxy-Polyester Hybrid Powders
> Powder Coating—From Particle to Performance | Article 07 of 32 | Polyurethane, Acrylic, Fluoropolymer, and Specialty Powders
> Powder Coating—From Particle to Performance | Article 08 of 32 | Selecting the Right Powder for the Application
> Powder Coating—From Particle to Performance | Article 09 of 32 | Why Surface Preparation Determines Coating Performance
> Powder Coating—From Particle to Performance | Article 10 of 32 | Preparing Steel, Aluminum, and Galvanized Surfaces
> Powder Coating—From Particle to Performance | Article 11 of 32 | Mechanical Surface Preparation for Powder Coating
> Powder Coating—From Particle to Performance | Article 12 of 32 | Chemical Pretreatment, Rinsing, and Dry-Off
> Powder Coating—From Particle to Performance | Article 13 of 32 | How Electrostatic Powder Coating Works
> Powder Coating—From Particle to Performance | Article 14 of 32 | Corona-Charging Powder Guns
> Powder Coating—From Particle to Performance | Article 15 of 32 | Tribostatic Powder Application
> Powder Coating—From Particle to Performance | Article 16 of 32 | Fluidized-Bed Powder Coating
> Powder Coating—From Particle to Performance | Article 17 of 32: Anatomy of a Manual Powder-Coating System
> Powder Coating—From Particle to Performance | Article 18 of 32: Anatomy of an Automatic Powder-Coating System
> Powder Coating—From Particle to Performance | Article 20 of 32: Powder Feed, Recovery, Reclaim, and Color Change
> Powder Coating—From Particle to Performance | Article 21 of 32: Compressed-Air Quality for Powder-Coating Equipment
> Powder Coating—From Particle to Performance | Article 22 of 32: How to Set Up and Start a Powder-Coating System
> Powder Coating—From Particle to Performance | Article 23 of 32: Setting Powder Flow, Pattern Air, kV, and Current
> Powder Coating—From Particle to Performance | Article 24 of 32: Professional Manual Powder-Gun Technique
> Powder Coating—From Particle to Performance | Article 25 of 32: Setting Up Automatic Guns and Reciprocators
> Powder Coating—From Particle to Performance | Article 26 of 32: Faraday-Cage Effect, Back Ionization, and Poor Coverage
> Powder Coating—From Particle to Performance | Article 27 of 32: Curing Powder Coating—Time at Metal Temperature
> Powder Coating—From Particle to Performance | Article 29 of 32: Measuring Powder-Coating Film Thickness
> Powder Coating—From Particle to Performance | Article 30 of 32: Testing Adhesion, Cure, Gloss, Color, and Appearance
> Powder Coating—From Particle to Performance | Article 31 of 32: Powder-Coating Defects and Corrective Action
> Powder Coating—From Particle to Performance | Article 32 of 32: Powder-Coating Safety, Housekeeping, and Preventive Maintenance
> Powder Coating—From Particle to Performance | Final Course Assessment
> Powder Coating—From Particle to Performance | Certificate of Completion
> Finishing Quality - From Spec to Sign-Off | AirSprayTech Academy
> Finishing Quality—From Spec to Sign-Off | Article 01 of 28: Quality Begins with the Specification
> Finishing Quality—From Spec to Sign-Off | Article 02 of 28: From Specification to Control Plan
> Finishing Quality—From Spec to Sign-Off | Article 03 of 28: Document Control and Traceability
> Finishing Quality—From Spec to Sign-Off | Article 04 of 28: Incoming Materials and Receiving Inspection
> Finishing Quality—From Spec to Sign-Off | Article 05 of 28: Incoming Process Water Quality
> Finishing Quality—From Spec to Sign-Off | Article 06 of 28: Process Water Treatment Systems
> Finishing Quality—From Spec to Sign-Off | Article 07 of 28 Treating and Releasing Finishing Wastewater
> Finishing Quality—From Spec to Sign-Off | Article 08 of 28: Surface Cleaning and Contamination Control
> Finishing Quality—From Spec to Sign-Off | Article 09 of 28 Surface Pretreatment and Conversion Coating Control
> Finishing Quality—From Spec to Sign-Off | Article 10 of 28 Coating Material Storage, Mixing, and Conditioning
> Finishing Quality—From Spec to Sign-Off | Article 11 of 28 Compressed-Air Quality and System Control
> Finishing Quality—From Spec to Sign-Off | Article 12 of 28 Temperature, Humidity, and Environmental Control
> Finishing Quality—From Spec to Sign-Off | Article 13 of 28 Application Equipment Setup and Process Verification
> Finishing Quality—From Spec to Sign-Off | Article 14 of 28 Wet-Film Thickness and Application Control
> Finishing Quality—From Spec to Sign-Off | Article 15 of 28 Dry-Film Thickness Measurement and Control
> Finishing Quality—From Spec to Sign-Off | Article 16 of 28 Cure Verification and Oven Performance
> Finishing Quality—From Spec to Sign-Off | Article 17 of 28 Appearance, Color, Gloss, and Texture Inspection
> Finishing Quality—From Spec to Sign-Off | Article 18 of 28 Coating Adhesion Testing and Interpretation
> Finishing Quality—From Spec to Sign-Off | Article 19 of 28 Hardness, Impact, Flexibility, and Abrasion Testing
> Finishing Quality—From Spec to Sign-Off | Article 20 of 28 Corrosion, Chemical, and Environmental Exposure Testing
> Finishing Quality—From Spec to Sign-Off | Article 21 of 28 Holiday, Porosity, and Coating-Continuity Testing
> Finishing Quality—From Spec to Sign-Off | Article 22 of 28 Building and Controlling the In-House Finishing Laboratory
> Finishing Quality—From Spec to Sign-Off | Article 23 of 28 Sampling Plans and Inspection Frequency
> Finishing Quality—From Spec to Sign-Off | Article 24 of 28 Building the Finishing Process Data Highway
> Finishing Quality—From Spec to Sign-Off | Article 25 of 28 Nonconformance, Root Cause, and Corrective Action
> Finishing Quality—From Spec to Sign-Off | Article 26 of 28 Final Product Audit, Acceptance, and Release
> Finishing Quality—From Spec to Sign-Off | Article 27 of 28 Build a Quality Team That Includes the People Doing the Work
> Finishing Quality—From Spec to Sign-Off | Article 28 of 28 Your Vendors Are Part of the Quality Team
> Finishing Quality—From Spec to Sign-Off | Final Assessment
> Finishing Quality—From Spec to Sign-Off | Certificate Request
> Paint Shop Planning - From Floor Plan to First Spray
> Paint Shop Planning—From Floor Plan to First Spray | Article 02 of 28 | Build a Project Team Before You Build the Shop
> Paint Shop Planning—From Floor Plan to First Spray | Article 03 of 28 | Meet the Authority Having Jurisdiction Early
> Paint Shop Planning—From Floor Plan to First Spray | Article 04 of 28 | Creating the Owner’s Project Requirements
> Paint Shop Planning—From Floor Plan to First Spray | Article 05 of 28 | Understanding NFPA 33 and Spray-Application Fire Protection
> Paint Shop Planning—From Floor Plan to First Spray | Article 06 of 28 | Understanding the NEC in a Paint Shop
> Paint Shop Planning—From Floor Plan to First Spray | Article 07 of 28 | Flammable and Combustible Liquid Storage
> Paint Shop Planning—From Floor Plan to First Spray | Article 08 of 28 | Building, Fire, and Mechanical Codes
> Paint Shop Planning—From Floor Plan to First Spray | Article 09 of 28 | Environmental Permits and Emissions Planning
> Paint Shop Planning—From Floor Plan to First Spray | Article 10 of 28 | Planning the Shop Layout and Product Flow
> Paint Shop Planning—From Floor Plan to First Spray | Article 11 of 28 | Spray-Booth and Preparation-Station Selection
> Paint Shop Planning—From Floor Plan to First Spray | Article 12 of 28 | Air-Makeup and Exhaust-System Planning
> Paint Shop Planning—From Floor Plan to First Spray | Article 13 of 28 | Planning the Compressed-Air System
> Paint Shop Planning—From Floor Plan to First Spray | Article 14 of 28 | Electrical Service, Controls, and Hazardous Locations
> Paint Shop Planning—From Floor Plan to First Spray | Article 15 of 28 | Natural Gas, Heating, and Curing Requirements
> Paint Shop Planning—From Floor Plan to First Spray | Article 16 of 28 | Fire Suppression, Detection, and Emergency Systems
> Paint Shop Planning—From Floor Plan to First Spray | Article 17 of 28 | Writing an Equipment Specification Vendors Can Quote
> Paint Shop Planning—From Floor Plan to First Spray | Article 18 of 28 | How to Compare Paint-Booth Proposals
> Paint Shop Planning—From Floor Plan to First Spray | Article 19 of 28 | Who Is Responsible for What?
> Paint Shop Planning—From Floor Plan to First Spray | Article 20 of 28 | Site Preparation and Construction Coordination
> Paint Shop Planning—From Floor Plan to First Spray | Article 21 of 28 | Change Orders: Where Paint-Shop Budgets Go to Die
> Paint Shop Planning—From Floor Plan to First Spray | Article 22 of 28 | Pre-Startup Inspection and Documentation
> Paint Shop Planning—From Floor Plan to First Spray | Article 23 of 28 | Testing Booth Airflow and Pressure
> Paint Shop Planning—From Floor Plan to First Spray | Article 24 of 28 | Testing Safety Interlocks and Emergency Controls
> Paint Shop Planning—From Floor Plan to First Spray | Article 25 of 28 | Commissioning the Complete Paint Shop
> Paint Shop Planning—From Floor Plan to First Spray | Article 26 of 28 | Training Operators and Maintenance Personnel
> Paint Shop Planning—From Floor Plan to First Spray | Article 27 of 28 | Final Acceptance: Do Not Sign Off Until It Performs
> Paint Shop Planning—From Floor Plan to First Spray | Article 28 of 28 | Planning for Maintenance, Expansion, and the Next Ten Years
> Paint Shop Planning—From Floor Plan to First Spray | Article 01 of 28 | Before You Buy a Booth: Define the Finishing Process
> Paint Shop Planning—From Floor Plan to First Spray | Final Assessment
> Paint Shop Planning—From Floor Plan to First Spray | Certificate of Completion Request
> Automotive Refinish - From Repair Plan to Road Ready
> Automotive Refinish—From Repair Plan to Road Ready | Article 01 of 28 | Start Before the Sandpaper: Vehicle Intake and Refinish Planning
> Automotive Refinish—From Repair Plan to Road Ready | Article 02 of 28 | PPE Is Part of the Process: Protecting the Automotive Painter
> Automotive Refinish—From Repair Plan to Road Ready | Article 03 of 28 | Fire, Fumes, and Ignition Sources: Everyday Refinish-Shop Safety
> Automotive Refinish—From Repair Plan to Road Ready | Article 04 of 28 | A Clean Shop Paints Cleaner Cars: Housekeeping and Contamination Control
> Automotive Refinish—From Repair Plan to Road Ready | Article 05 of 28 | Know What You Are Painting: Automotive Substrate Identification
> Automotive Refinish—From Repair Plan to Road Ready | Article 06 of 28 | Clean Before You Cut: Washing, Degreasing, and Contamination Removal
> Automotive Refinish—From Repair Plan to Road Ready | Article 07 of 28 | Stop Corrosion Before It Starts: Bare Metal and Corrosion Protection
> Automotive Refinish—From Repair Plan to Road Ready | Article 08 of 28 | Sand With a Purpose: Abrasives, Grit Selection, and Surface Profiles
> Automotive Refinish—From Repair Plan to Road Ready | Article 09 of 28 | Build It Straight: Fillers, Glazes, Primers, and Sealers
> Automotive Refinish—From Repair Plan to Road Ready | Article 10 of 28 | Mask the Repair, Not the Mistake: Paper, Plastic, Tape, and Technique
> Automotive Refinish—From Repair Plan to Road Ready | Article 11 of 28 | Choose the Complete System: Modern Automotive-Refinish Materials
> Automotive Refinish—From Repair Plan to Road Ready | Article 12 of 28 | Control the Mix: Paint Storage, Mixing Rooms, and Material Management
> Automotive Refinish—From Repair Plan to Road Ready | Article 13 of 28 | Match It Before You Spray It: Color Tools, Spray-Outs, and Color Acceptance
> Automotive Refinish—From Repair Plan to Road Ready | Article 14 of 28 | Choose the Right Spray Gun: Match the Equipment to the Finish
> Automotive Refinish—From Repair Plan to Road Ready | Article 15 of 28 | Feed the Finish: Air-Compressor Operation and Maintenance
> Automotive Refinish—From Repair Plan to Road Ready | Article 16 of 28 | Keep the Gun Honest: Spray Equipment Operation and Maintenance
> Automotive Refinish—From Repair Plan to Road Ready | Article 17 of 28 | Paint With a Plan: Professional Basecoat and Clearcoat Application
> Automotive Refinish—From Repair Plan to Road Ready | Article 18 of 28 | Control the Booth: Airflow, Filters, Lighting, and Maintenance
> Automotive Refinish—From Repair Plan to Road Ready | Article 19 of 28 | Balance the Booth: Air-Makeup Unit Operation and Maintenance
> Automotive Refinish—From Repair Plan to Road Ready | Article 20 of 28 | Cure It by the Numbers: Flash, Bake, and Return-to-Service
> Automotive Refinish—From Repair Plan to Road Ready | Article 21 of 28 | Correct Without Creating: Denibbing, Sanding, and Polishing
> Automotive Refinish—From Repair Plan to Road Ready | Article 22 of 28 | Put It Back Right: Reassembly Without Damaging the Finish
> Automotive Refinish—From Repair Plan to Road Ready | Article 23 of 28 | Inspect It Before the Customer Does: Final Quality Control
> Automotive Refinish—From Repair Plan to Road Ready | Article 24 of 28 | Deliver More Than Shine: Customer Handoff and Fresh-Paint Care
> Automotive Refinish—From Repair Plan to Road Ready | Article 25 of 28 | Control the Waste Stream: Paint, Solvent, Filters, and Compliance
> Automotive Refinish—From Repair Plan to Road Ready | Article 26 of 28 | Troubleshoot the Process: Find the Cause Before Repainting
> Automotive Refinish—From Repair Plan to Road Ready | Article 27 of 28 | Make Quality Repeatable: Procedures, Training, and Team Accountability
> Automotive Refinish—From Repair Plan to Road Ready | Article 28 of 28 | Road Ready Is Earned: Audit the Complete Refinish Process
> Automotive Refinish—From Repair Plan to Road Ready | Final Assessment
> Automotive Refinish—From Repair Plan to Road Ready | Certificate of Completion Request
> Corrosion Protection for Industrial Coating Contractors - 00 Course Overview
> Corrosion Protection for Industrial Coating Contractors - Article 01: Understanding Corrosion
> Corrosion Protection for Industrial Coating Contractors - Article 02: Common Forms of Corrosion
> Corrosion Protection for Industrial Coating Contractors - Article 03: Evaluating the Structure and Service Environment
> Corrosion Protection for Industrial Coating Contractors - Article 04: Protective Coatings as the Primary Barrier
> Corrosion Protection for Industrial Coating Contractors - Article 05: Selecting the Correct Coating System
> Corrosion Protection for Industrial Coating Contractors - Article 06: Surface Cleanliness and Contaminant Testing
> Corrosion Protection for Industrial Coating Contractors - Article 07: Abrasive Blasting and Surface-Preparation Standards
> Corrosion Protection for Industrial Coating Contractors - Article 08: Surface Profile and Anchor Pattern
> Corrosion Protection for Industrial Coating Contractors - Article 09: Environmental Conditions and Dew Point Control
> Corrosion Protection for Industrial Coating Contractors - Article 10: Selecting Coating Systems for the Service Environment
> Corrosion Protection for Industrial Coating Contractors - Article 11: Primers and Their Role in Corrosion Protection
> Corrosion Protection for Industrial Coating Contractors - Article 12: Intermediate Coats, Finish Coats, and Stripe Coating
> Corrosion Protection for Industrial Coating Contractors - Article 13: Coating Application Methods and Spray Technique
> Corrosion Protection for Industrial Coating Contractors - Article 14: Coating Mixing, Thinning, Induction Time, and Pot Life
> Corrosion Protection for Industrial Coating Contractors - Article 15: Wet Film and Dry Film Thickness Control
> Corrosion Protection for Industrial Coating Contractors - Article 16: Holidays, Pinholes, and Discontinuity Testing
> Corrosion Protection for Industrial Coating Contractors - Article 17: Coating Adhesion Testing and Failure Interpretation
> Corrosion Protection for Industrial Coating Contractors - Article 18: Coating Defects and Failure Diagnosis
> Corrosion Protection for Industrial Coating Contractors - Article 19: How Coatings and Cathodic Protection Work Together
> Corrosion Protection for Industrial Coating Contractors - Article 20: Final Inspection, Repair Verification, and Project Documentation
> Corrosion Protection for Industrial Coating Contractors - Final Assessment
> Corrosion Protection for Industrial Coating Contractors - Final Certificate of Completion Request
> Protective Linings for Industrial Coating Contractors | 00 - Course Overview
> Protective Linings for Industrial Coating Contractors | Article 01 of 20 - Protective Linings: What They Are and Why They Fail
> Protective Linings for Industrial Coating Contractors | Article 02 of 20 - Understanding the Lining Service Environment
> Protective Linings for Industrial Coating Contractors | Article 04 of 20 - Selecting a Lining for the Material Being Contained
> Protective Linings for Industrial Coating Contractors | Article 05 of 20 - Epoxy Linings and Where They Are Used
> Protective Linings for Industrial Coating Contractors | Article 06 of 20 - Novolac Epoxy Linings for Severe Chemical Service
> Protective Linings for Industrial Coating Contractors | Article 07 of 20 - Vinyl Ester and Polyester Lining Systems
> Protective Linings for Industrial Coating Contractors | Article 08 of 20 - Polyurethane, Polyurea, and Elastomeric Linings
> Protective Linings for Industrial Coating Contractors | Article 09 of 20 - Cementitious and Specialty Lining Systems
> Protective Linings for Industrial Coating Contractors | Article 10 of 20 - Inspecting Steel and Concrete Before Lining Work Begins
> Protective Linings for Industrial Coating Contractors | Article 11 of 20 - Preparing Steel for Protective-Lining Application
> Protective Linings for Industrial Coating Contractors | Article 12 of 20 - Preparing Concrete for Protective Linings
> Protective Linings for Industrial Coating Contractors | Article 13 of 20 - Moisture in Concrete: When a Lining Should Not Be Applied
> Protective Linings for Industrial Coating Contractors | Article 14 of 20 - Environmental Conditions, Dew Point, and Condensation Control
> Protective Linings for Industrial Coating Contractors | Article 15 of 20 - Mixing, Induction Time, Pot Life, and Material Temperature
> Protective Linings for Industrial Coating Contractors | Article 16 of 20 - Applying High-Build and Plural-Component Linings
> Protective Linings for Industrial Coating Contractors | Article 17 of 20 - Stripe Coating, Edges, Welds, Penetrations, and Difficult Areas
> Protective Linings for Industrial Coating Contractors | Article 18 of 20 - Film Thickness, Recoat Windows, Curing, and Return to Service
> Protective Linings for Industrial Coating Contractors | Article 19 of 20 - Inspecting Protective Linings
> Protective Linings for Industrial Coating Contractors | Article 20 of 20 - Final Acceptance, Repairs, and Lining Maintenance
> Protective Linings for Industrial Coating Contractors - Final Assessment
> Protective Linings for Industrial Coating Contractors | Certificate of Completion Request
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | 00 - Course Overview
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 01 of 20 - Why Moisture Causes Coating and Flooring Fail
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 03 of 20 - Moisture Vapor Versus Hydrostatic Pressure
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 02 of 20 - How Moisture Moves Through Concrete
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 04 of 20 - Sources of Moisture in Concrete Slabs and Str
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 05 of 20 - Recognizing Moisture-Related Coating Failures
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 06 of 20 - Relative-Humidity Testing of Concrete Slabs
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 07 of 20 - Calcium-Chloride Moisture-Vapor-Emission Test
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 08 of 20 - Electronic Moisture Meters and Surface-Moistu
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 09 of 20 - Concrete pH and Alkalinity at the Bond Line
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 10 of 20 - Dew Point, Condensation, and Environmental Co
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 11 of 20 - Osmotic Blistering, Delamination, and Efflore
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 12 of 20 - When a Coating Should Not Be Applied
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 13 of 20 - Selecting a Moisture-Mitigation System
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 14 of 20 - Surface Preparation for Moisture-Mitigation M
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 15 of 20 - Applying Moisture-Mitigation Membranes
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 16 of 20 - Pinholes, Holidays, and Membrane Inspection
> Moisture Vapor Barriers and Mitigation Membranes for Industrial Coating Contractors | Article 17 of 20 - Primers, Underlayments, Adhesives, and System
> Moisture Vapor Management | 18 - Repairing Coating and Flooring Failures
> Moisture Vapor Management | 19 - Documentation, Warranties, and Contractor Liability
> Moisture Vapor Management | 20 - Complete Moisture-Management Plan
> Moisture Vapor Management | Course Assessment
> Moisture Vapor Management | Certificate Request
> Commercial and Industrial Floor Coatings - Course Overview
> Commercial and Industrial Floor Coatings | Article 01 of 24 | What Floor Coatings Must Do
> Commercial and Industrial Floor Coatings | Article 02 of 24 | Defining the Service Environment
> Commercial and Industrial Floor Coatings | Article 03 of 24 | Evaluating Existing Concrete and Previous Floors
> Commercial and Industrial Floor Coatings | Article 04 of 24 | Concrete Moisture and Floor-Coating Failure
> Commercial and Industrial Floor Coatings | Article 05 of 24 | Removing Oil, Grease and Chemical Contamination
> Commercial and Industrial Floor Coatings | Article 06 of 24 | Mechanical Surface Preparation
> Commercial and Industrial Floor Coatings | Article 07 of 24 | Concrete Surface Profile and Preparation Acceptance
> Commercial and Industrial Floor Coatings | Article 08 of 24 | Repairing Cracks, Joints, Spalls and Damaged Concrete
> Commercial and Industrial Floor Coatings | Article 09 of 24 | Primers, Patches, Underlayments and Moisture Mitigation
> Commercial and Industrial Floor Coatings | Article 10 of 24 | Understanding Resinous Floor-Coating Chemistries
> Commercial and Industrial Floor Coatings | Article 11 of 24 | Epoxy Floor-Coating Systems
> Commercial and Industrial Floor Coatings | Article 12 of 24 | Polyurethane and Polyaspartic Floor Coatings
> Commercial and Industrial Floor Coatings | Article 13 of 24
> Commercial and Industrial Floor Coatings | Article 14 of 24
> Commercial and Industrial Floor Coatings | Article 15 of 24
> Commercial and Industrial Floor Coatings | Article 16 of 24
> Commercial and Industrial Floor Coatings | Article 17 of 24
> Commercial and Industrial Floor Coatings | Article 18 of 24
> Commercial and Industrial Floor Coatings | Article 19 of 24
> Commercial and Industrial Floor Coatings | Article 20 of 24
> Commercial and Industrial Floor Coatings | Article 21 of 24 | Warehouse, Manufacturing, Vehicle and Aircraft-Hangar Floors
> Commercial and Industrial Floor Coatings | Article 22 of 24 | Food, Beverage, Sanitary, Healthcare and Cleanroom Floors
> Commercial and Industrial Floor Coatings | Article 24 of 24 | Estimating, Documentation, Warranties, Maintenance and Final Acceptance
|
|